ASCII - Command KTN    
Syntax Transmit KTN [Data]    
Syntax Receive KTN <Data>   Available in  
Type Variable rw   MMI Yes
ASCII Format Float   CANBus Object Number 362F (hex)
DIM ms   PROFIBUS PNU 1903 (dec) IND = 1 (dec)
Range 0.2 ... 2   DPR 303 (dec)
Default 0.6    
Opmode All   Data Type Bus/DPR Integer32
Drive State -   Weighting 1000
Start Firmware 1.0    
Configuration No   Last Change of this Object 1.0
Function Group current loop   EEPROM Yes
Short Description Current Controller Integral-Action Time

Description

The integral-action time (integration time constant) of the current control loop.