ASCII - Command | PMODE | |||
Syntax Transmit | PMODE [Data] | |||
Syntax Receive | PMODE <Data> | Available in | ||
Type | Variable rw | MMI | Yes | |
ASCII Format | Integer8 | CANBus Object Number | 35CD (hex) | |
DIM | - | PROFIBUS PNU | 1805 (dec) IND = 1 (dec) | |
Range | 0 .. 8 | DPR | 205 (dec) | |
Default | (0) 1 | |||
Opmode | All | Data Type Bus/DPR | Integer32 | |
Drive State | Disabled + Reset (Coldstart) | Weighting | ||
Start Firmware | 1.0 | |||
Configuration | Yes | Last Change of this Object | 2.14 | |
Function Group | drive configuration | EEPROM | Yes | |
Short Description | Line Phase Mode |
Description
Theis parameter configurate the line phase mode only for the S30x - not available on S34x! PMODE=0 single phase operation (current limit) for S300/S700 PMODE=1 three phase operation, current limited and warning n05 in case of network phase missing PMODE=2 three phase operation, error message F19 in case of DC bus break down PMODE=3 three phase operation, current limited and warning n05 in case of network phase missing PMODE=4 direct DC feed PMODE=5 such als PMODE=1, the warning or fault is generated by enabled drive PMODE=6 such als PMODE=2, the warning or fault is generated by enabled drive PMODE=7 such als PMODE=3, the warning or fault is generated by enabled drive PMODE=8 reserved If the current limiting is activated, it only applies to periods of acceleration. A braking operation can still be carried out at full current. |