ASCII - Command VBUSBAL    
Syntax Transmit VBUSBAL [Data]    
Syntax Receive VBUSBAL <Data>   Available in  
Type Variable rw   MMI Yes
ASCII Format Integer16   CANBus Object Number 361B (hex)
DIM - / V   PROFIBUS PNU 1883 (dec) IND = 1 (dec)
Range 0, 1, 2, 3, 4, 40..750   DPR 283 (dec)
Default depends on type of drive    
Opmode All   Data Type Bus/DPR Integer16
Drive State Disabled + Reset (Coldstart)   Weighting  
Start Firmware 1.0    
Configuration Yes   Last Change of this Object 2.8
Function Group drive configuration   EEPROM Yes
Short Description Maximum Line Voltage

Description

This setting is for the maximum permissible voltage for the motor. For instance, if a motor that is rated for a 400V supply is connected to the amplifier, then the setting must be VBUSBAL = 2 (400V). This sets regen and overvoltage thresholds in the amplifier to acceptable values for the motor. This ensures that the motor windings are not damaged.


VBUSBAL - Setting in the range of 40 to 750 are used to choose the maximum network voltage.
In this case ist VBUSMAX = 1,2 x VBUSBAL

only for S300:
VBUSBAL=0 (115 V) VBUSMAX = 235V, regen threshold = 200V

only for S300/S700:
VBUSBAL=1 (230 V) VBUSMAX = 455V, regen threshold = 400V
VBUSBAL=2 (400 V) VBUSMAX = 800V, regen threshold = 720V
VBUSBAL=3 (480 V) VBUSMAX = 900V, regen threshold = 840V

additional for S748/S772 since FW-version 5.67
VBUSBAL=4 (480V) VBUSMAX = 900V, regen threshold = 790V

The default value of VBUSBAL depends on the type of the drive:
S303,S306,S310 : VBUSBAL=2
S341,S343,S346 : VBUSBAL=3
S700: 230V version VBUSBAL=1
S700: 400V version VBUSBAL=3
S748/S772: since FW 5.67 VBUSBAL=4