ASCII - Command VOSPD    
Syntax Transmit VOSPD [Data]    
Syntax Receive VOSPD <Data>   Available in  
Type Variable rw   MMI No
ASCII Format Float   CANBus Object Number 3627 (hex)
DIM rpm   PROFIBUS PNU 1895 (dec) IND = 1 (dec)
Range 0.0 .. 1.2*MSPEED   DPR 295 (dec)
Default 3600    
Opmode All   Data Type Bus/DPR Integer32
Drive State -   Weighting  
Start Firmware 1.0    
Configuration No   Last Change of this Object 1.0
Function Group position loop   EEPROM Yes
Short Description Overspeed

Description

The VOSPD parameter sets the overspeed threshold. As soon as the actual velocity exceeds this limit, the fault message F08 (overspeed) is generated and the output stage is disabled.