| ASCII - Command | ENCVON | |||
| Syntax Transmit | ENCVON [Data] | |||
| Syntax Receive | ENCVON <Data> | Available in | ||
| Type | Variable rw | MMI | No | |
| ASCII Format | - | CANBus Object Number | 3546 (hex) | |
| DIM | - | PROFIBUS PNU | 1670 (dec) IND = 1 (dec) | |
| Range | 0 ... 2 | DPR | 70 (dec) | |
| Default | 0 | |||
| Opmode | All | Data Type Bus/DPR | - | |
| Drive State | Disabled + Reset (Coldstart) | Weighting | ||
| Start Firmware | 0.73 | |||
| Configuration | Yes | Last Change of this Object | 1.0 | |
| Function Group | other commands | EEPROM | - | |
| Short Description | power supply for the external encoder (connector X1 | |||
Description
| The command ENCVON switches the power supply for the external encoder on/off (connector X1).ENCVON=1 means 5V power supply, ENCVON=2 have to be used for 12V power supply.These settings can only be used when no external encoder was configured (ENDAT or HIPERFACE with FBTYPE/GEARMODE/EXTPOS). In case of encoder configuration the power supply required by this encoder has a higher priority as the setting ENCVON. The setting ENCVON=2 (12V power supply) is only possible when the SENSE wire was not recognized. |