ASCII - Command VSCALE2    
Syntax Transmit VSCALE2 [Data]    
Syntax Receive VSCALE2 <Data>   Available in  
Type Variable rw   MMI Yes
ASCII Format Integer16   CANBus Object Number 362A (hex)
DIM rpm / 10 V   PROFIBUS PNU 1898 (dec) IND = 1 (dec)
Range -16000 .. 16000 (for VUNIT=0)   DPR 298 (dec)
Default 3000 (for VUNIT=0)    
Opmode 1   Data Type Bus/DPR Integer16
Drive State -   Weighting  
Start Firmware 1.0    
Configuration No   Last Change of this Object 2.10
Function Group analog I/O   EEPROM Yes
Short Description SW2 velocity scaling factor

Description

If the analog input 2 is used as the setpoint input for velocity control, then the VSCALE2 parameter can be used to set the scaling of the input voltage.
A 10V velocity setpoint input at input 2 produces a velocity of VSCALE2.

Attention: VSCALE1/VSCALE2 may not be smaller than 2UPM!