ASCII - Command CLRFAULT    
Syntax Transmit CLRFAULT    
Syntax Receive CLRFAULT   Available in  
Type Command   MMI Yes
ASCII Format -   CANBus Object Number 3518 (hex)
DIM -   PROFIBUS PNU 1624 (dec) IND = 1 (dec)
Range -   DPR 24 (dec)
Default -    
Opmode All   Data Type Bus/DPR -
Drive State -   Weighting  
Start Firmware 1.20    
Configuration No   Last Change of this Object 1.3
Function Group Amplifier   EEPROM -
Short Description Clear Drive Fault

Description

The CLRFAULT command cancels the fault status of an amplifier. A hardware or software reset of the amplifier is carried out, depending on the type of fault that is present.
After a software reset the amplifier is immediately ready for operation, after a hardware reset the complete initialization phase must be gone through first (as for power-on).
As well as amplifier faults (display Fxx), the following warnings are also deleted.
- contouring/following error
- threshold monitoring

With the selection CLRWARN=1 (separate cancellation of warnings) this command will delete all warnings that are present.
A listing of all possible fault/error messages, with information on the hardware/software reset required, can be found in the description of the ERRCODE command.

The CLRFAULT command can either be implemented through the ASCII channel (CLRFAULT command ) or via the CAN/PROFIBUS (with the “cancel fault” bit in the control word), or through a digital input (“Controller reset” function).