Screen Page "SERCOS"
Address
ASCII: ADDR |
Default: 0 |
valid for all OPMODES |
The address mark the Sercos station address of the drive, within the Sercos
communication The address can changed between 0 and 63 in the screen "Basic settings".
Address
0 designates the drive as a repeater on the Sercos ring.
Baud Rate
ASCII: SBAUD |
Default: 4MBaud |
valid for all OPMODES |
In this field it is possible to set the Sercos baud rate.
LWL-Length
ASCII: SLEN |
Default: 5m |
valid for all OPMODES |
Within this parameter it is possible to change the optical power of the
transmit output of the drive, to the next station in the ring. The optical
power can set for the length of plastic optical cable, in meters, from
1 to 45 meters. If the optical power is not adjusted properly, there will
be errors in the telegram transmission, and the red error LED on the drive
will light. In normal communication, the green transmit and receive LEDs
will light (referring to the LED of the optical transmission).
Phase
ASCII: SPHAS |
Default: - |
valid for all OPMODES |
This field display the actual phase of the Sercos communication.
Status
ASCII: SSTAT |
Default: - |
valid for all OPMODES |
This field displays the actual status of the Sercos communication, according
the Sercos status-word in text format.
SERCOS SERVICE
With this button you can open the "Sercos Service" screen page.