ASCII - Command VBUSLIM    
Syntax Transmit VBUSLIM [Data]    
Syntax Receive VBUSLIM <Data>   Available in  
Type Variable rw   MMI No
ASCII Format -   CANBus Object Number 35F5 (hex)
DIM %   PROFIBUS PNU 1845 (dec) IND = 1 (dec)
Range 70...95   DPR 245 (dec)
Default 90    
Opmode All   Data Type Bus/DPR -
Drive State     Weighting  
Start Firmware      
Configuration No   Last Change of this Object 2.6
Function Group drive configuration   EEPROM Yes
Short Description threshold of the phase failure monitoring

Description

This parameter describes th threshold of the phase failure monitoring function.

The dimension of this bar is % of the avarage DC bus. If the bar of the DC bus for min. 25msec fall below, there will be generatet a warning (n05) or a fault (F19) depending on the settings of PMODE.