| ASCII - Command | CPHASE | |||
| Syntax Transmit | CPHASE [Data] | |||
| Syntax Receive | CPHASE <Data> | Available in | ||
| Type | Variable rw | MMI | No | |
| ASCII Format | Integer8 | CANBus Object Number | 358B (hex) | |
| DIM | PROFIBUS PNU | 1739 (dec) IND = 1 (dec) | ||
| Range | 0 .. 0x7FFF | DPR | 139 (dec) | |
| Default | 1 | |||
| Opmode | All | Data Type Bus/DPR | Integer8 | |
| Drive State | Disabled + Reset (Coldstart) | Weighting | ||
| Start Firmware | 2.3 | |||
| Configuration | Yes | Last Change of this Object | 2.13 | |
| Function Group | drive configuration | EEPROM | Yes | |
| Short Description | configuration of fault monitoring | |||
Description
| The parameter CPHASE configurates the error monitoring of the motor phases, I/O optioncard, feedback amplitudes (SinCos and resolver) as well the regen fault. Have a look to STATCODE * |
||
| Bit | value | description |
| 0 | 0x0001 | =0 motor cable break supervision =1 no motor cable break supervision |
| 1 | 0x0002 | =0 amplitude supervision is active =1 no amplitude supervision |
| 2 | 0x0004 | =0 I/O card error/Warning are displayed =1 no I/O card error/Warning (since FW 5.45) |
| 3 | 0x0008 | =0 regen error supervision is active =1 no regen error supervision (since FW 5.67) |
| 4 | 0x0010 | =0 old resolver error supervision =1 extended resolver error supervision (since FW 5.78) |
| 5 | 0x0020 | =0 no resolver gradient check =1 resolver gradient check active (only when extended resolver error supervision active) (since FW 5.78) |
| 6 | 0x0040 | reserved |
| 7 | 0x0080 | = 1 no monitoring of the bus-off fault (F23) |