ASCII - Command | PBALMAX | |||
Syntax Transmit | PBALMAX [Data] | |||
Syntax Receive | PBALMAX <Data> | Available in | ||
Type | Variable rw | MMI | Yes | |
ASCII Format | Integer32 | CANBus Object Number | 35C1 (hex) | |
DIM | W | PROFIBUS PNU | 1793 (dec) IND = 1 (dec) | |
Range | see Manual | DPR | 193 (dec) | |
Default | ||||
Opmode | All | Data Type Bus/DPR | Integer32 | |
Drive State | - | Weighting | ||
Start Firmware | 1.0 | |||
Configuration | No | Last Change of this Object | 2.10 | |
Function Group | drive configuration | EEPROM | Yes | |
Short Description | Maximum Regen Power |
Description
This parameter can be used to limit the continuous power dissipated in the regen resistor. If the actual value of the power in the regen resistor exceeds the preset maximum value, then the regen resistor is switched off. This may trigger the fault message “Overvoltage” as a result. If the maximum value is too high, the regen resistor may be overloaded. Defaultwerte: with PBALRES = 0 SR 303, SR 341 20 W SR 306, SR 310, SR 343, SR 346 50 W with PBALRES >= 1 SR 303, SR 341 300W SR 306, SR 310, SR 343, SR 346 1000 W Note: From the perspective of the drive is PBALMAX the maximum power that is released permanently to the regen resistor. From the viewpoint of the regen resistance is this the rated power. |