| ASCII - Command | AN1TRIG | |||
| Syntax Transmit | AN1TRIG [Data] | |||
| Syntax Receive | AN1TRIG <Data> | Available in | ||
| Type | Variable rw | MMI | No | |
| ASCII Format | Integer32 | CANBus Object Number | 36A1 (hex) | |
| DIM | - | PROFIBUS PNU | 2017 (dec) IND = 1 (dec) | |
| Range | Long Int | DPR | 417 (dec) | |
| Default | 100 | |||
| Opmode | All | Data Type Bus/DPR | Integer32 | |
| Drive State | - | Weighting | ||
| Start Firmware | 4.93 | |||
| Configuration | No | Last Change of this Object | 1.6 | |
| Function Group | Analog I/O | EEPROM | Yes | |
| Short Description | Scaling of the analog output 1 | |||
Description
| AN1TRIG scales the analog output. The scaling is done in %. Example: ANOUT1 = 1 Actual velocity AN1TRIG = 100 10V at the output at actual velocity=VLIM AN1TRIG = 50 5V at the output at actual velocity=VLIM AN1TRIG = 200 10V at the output at actual velocity=VLIM/2 If ANOUT1=8 is selected (constant voltage), AN1TRIG gives the voltage in mV. |