ASCII - Command VBUSBAL    
Syntax Transmit VBUSBAL [Data]    
Syntax Receive VBUSBAL <Data>   Available in  
Type Variable rw   MMI Yes
ASCII Format Integer16   CANBus Object Number 361B (hex)
DIM -   PROFIBUS PNU 1883 (dec) IND = 1 (dec)
Range 0, 1, 2   DPR 283 (dec)
Default 2    
Opmode All   Data Type Bus/DPR Integer16
Drive State -   Weighting  
Start Firmware 1.20    
Configuration No   Last Change of this Object 1.6
Function Group Basic Setup   EEPROM Yes
Short Description Maximum Line Voltage

Description

This setting is for the maximum permissible voltage for the motor. For instance, if a motor that is rated for a 400V supply is connected to the amplifier, then the setting must be VBUSBAL = 1 (400V). This sets regen and overvoltage thresholds in the amplifier to acceptable values for the motor. This ensures that the motor windings are not damaged.
If several amplifiers are connected to the supply with the DC-buses in parallel, then they must all have the same value for VBUSBAL. It must therefore be set to suit the motor with the lowest voltage rating.

VBUSBAL=0 (230 V) VBUSMAX=450V
VBUSBAL=1 (400 V) VBUSMAX=800V
VBUSBAL=2 (480 V) VBUSMAX=900V

The setting for the drive 40xM is limited to 0 (230V). The default setting is also 0.
The setting for the drive 44xM is limited to 0 (400V). The default setting is also 1.

VBUSBAL also changes DICONT and DIPEAK at following drive types (starting with firmware 4.94):

VBUSBAL = 0
443 DICONT = 3 DIPEAK = 9
446 DICONT = 6 DIPEAK = 12

VBUSBAL = 1
443 DICONT = 2 DIPEAK = 6
446 DICONT =4 DIPEAK = 8

VBUSBAL = 2
443 not possible
446 not possible