ASCII - Command VBUSMIN    
Syntax Transmit VBUSMIN [Data]    
Syntax Receive VBUSMIN <Data>   Available in  
Type Variable rw   MMI Yes
ASCII Format Integer16   CANBus Object Number 361D (hex)
DIM Volts   PROFIBUS PNU 1885 (dec) IND = 1 (dec)
Range 30 .. 800   DPR 285 (dec)
Default 100    
Opmode All   Data Type Bus/DPR Integer16
Drive State -   Weighting  
Start Firmware 1.20    
Configuration No   Last Change of this Object 1.3
Function Group Amplifier   EEPROM Yes
Short Description Minimum DC-bus Voltage

Description

VBUSMIN defines the lower threshold for monitoring the DC-bus voltage. The fault message F05 (undervoltage) is generated as soon as the DC-bus voltage goes below this threshold. Undervoltage monitoring is only active under the following conditions.
1. Output stage is enabled
2. Monitoring is activated UVLTMODE=1
3. MAINSBTB function is not active (OxMODE<>3)
4. The switch-off of the monitoring function by a digital input (INxMODE=21) is not active.