ASCII - Command | O1MODE | |||
Syntax Transmit | O1MODE [Data] | |||
Syntax Receive | O1MODE <Data> | Available in | ||
Type | Variable rw | MMI | Yes | |
ASCII Format | Integer8 | CANBus Object Number | 35AF (hex) | |
DIM | - | PROFIBUS PNU | 1775 (dec) IND = 1 (dec) | |
Range | 0 .. 50 | DPR | 175 (dec) | |
Default | 0 | |||
Opmode | All | Data Type Bus/DPR | Integer8 | |
Drive State | Disabled + Reset (Coldstart) | Weighting | ||
Start Firmware | 1.20 | |||
Configuration | Yes | Last Change of this Object | 2.0 | |
Function Group | Digital I/O | EEPROM | Yes | |
Short Description | Function of digital output 1 |
Description
The O1 command returns the state of the digital output 1 (0 = Low,1 = High). If no function is assigned to digital output 1 (O1MODE=0), then the High/Low state can be given out at output 1 by using the command “O1 1” or “O1 0”. |
||
Status | Function | Description |
O1MODE=0 | Off | OFF The state of the digital output 1 can be set/cleared by RS232/Fieldbus or Slot board |
O1MODE=1 | v_act<O1TRIG | As long as the absolute value for the motor velocity is lower than a preset value (O1TRIG), a HIGH-signal will be output. After the function has been selected you can enter the velocity in rpm in O1TRIG. The ouput is high, if V < O1TRIG and becomes low, if V > O1TRIG + 0.01 * MSPEED. The value unit is fixed by VUNIT |
O1MODE=2 | v_act>O1TRIG | As long as the absolute value for the motor velocity is higher than a preset value (O1TRIG), a HIGH-signal will be output. After the function has been selected you can enter the velocity in rpm in O1TRIG. The ouput is high, if V > O1TRIG and becomes low, if V < O1TRIG + 0.01 * MSPEED. The value unit is fixed by VUNIT |
O1MODE=3 | Mains-RTO | After switching on the mains supply, a HIGH-signal is output until the DC-link circuit is fully charged up. A LOW-signal is output when the charging of the DC-link circuit is finished. If the DC-link voltage falls below VBUSMIN value, then a HIGH-signal will be output. The “Undervoltage” monitoring is inactive. |
O1MODE=4 | Regen off | Signals if the preset regen power (screen page “Basic Setup”) is exceeded. |
O1MODE=5 | Sw_limit | This produces a HIGH-signal if a software limit-switch is reached (a preset function of the corresponding position register, set to “SW limit-switch 1” or “SW limit-switch 2” – the function is defined in the screen page “Position”). |
O1MODE=6 | Pos.>x | If the position (angular position of the motor shaft) exceeds a preset value (O1TRIG), a HIGH-signal will be output. After the function has been selected, you can enter the signaling posi-tion in increment (a number or fraction of motor turns N) as O1TRIG. Make the calculation according to the following equation: x = 1048576 *N *Inkr. Maximum possible entry value:x =2 31 = 2147483648, this corresponds to N = 2048 |
O1MODE=7 | InPos | When the target position for a motion task has been reached (the InPosition window PEINPOS), this is signaled by the output of a HIGH-signal. A cable break will not be detected. The width of the InPosition window for all the valid motion tasks is entered in the “Position data” screen page. If a sequence of motion tasks is performed one after another, then the signal for reaching the final position of the motion-task sequence will be output (target position of the last motion task). Signaling that the target position of each motion task has been reached, in a sequence of motion tasks, can be achieved with the function “16, Next_InPos”. |
O1MODE=8 | I_act<O1TRIG | The output is a HIGH-signal, as long as the absolute r.m.s. value of the actual current is lower than a defined value in mA (O1TRIG). After the function has been selected, you can enter the current value as O1TRIG in mA. |
O1MODE=9 | I_act>O1TRIG | The output is a HIGH-signal, as long as the absolute r.m.s. value of the actual current is higher than a defined value in mA (O1TRIG). After the function has been selected, you can enter the current value as O1TRIG in mA. |
O1MODE=10 | Ferror | If the position goes outside the preset contouring-error window, this is indicated by a LOW-signal. The width of the contouring-error window (PEMAX) is entered in the screen page “Position” for all the valid motion tasks. |
O1MODE=11 | I2T | If the preset I2T monitoring threshold (I2TLIM) is reached (screen page “Current” ) this is indicated by a HIGH-signal. |
O1MODE=12 | Posreg.1 | The preset function of the corresponding position register 1 (the function is defined in the screen page “Position”) is indicated by a HIGH-signal. |
O1MODE=13 | Posreg.2 | The preset function of the corresponding position register 2 (the function is defined in the screen page “Position”) is indicated by a HIGH-signal. |
O1MODE=14 | Posreg.3 | The preset function of the corresponding position register 3 (the function is defined in the screen page “Position”) is indicated by a HIGH-signal. |
O1MODE=15 | Posreg.4 | The preset function of the corresponding position register 4 (the function is defined in the screen page “Position”) is indicated by a HIGH-signal. |
O1MODE=16 | Next-InPos | The start of each motion task in an automatically executed sequence of motion tasks is signalled by an inversion of the output signal. The output produces a Low signal at the start of the first motion task of the motion task sequence. The type of message can be set by IN2PM |
O1MODE=17 | Error/Warn | The output produces a HIGH-signal if an error or a warning message is signaled by the servo amplifier. A list of the error messages can be found under ERRCODE. n32 has no effect to the output. |
O1MODE=18 | Error | The output produces a HIGH-signal if an error is signaled by the servo amplifier. A list of the error messages can be found under ERRCODE |
O1MODE=19 | DC_Link>O1TRIG | A HIGH-signal is output if the actual value of the DC-link voltage is higher than a defined value in volts (O1TRIG). After the function has been selected, you can enter the voltage value as O1TRIG in Volt.. |
O1MODE=20 | DC_Link < O1TRIG | A HIGH-signal is output if the actual value of the DC-link voltage is lower than a defined value in volts (O1TRIG). After the function has been selected, you can enter the voltage value in O1TRIG in Volt. |
O1MODE=21 | Powerstagestatus (Enable / Disable) | A HIGH-signal is output if the servo amplifier is enabled. To obtain the enable, the external Hardware Enable signal must be present, the Enable status must be set in the setup software (or via the fieldbus interface) and no errors must be present that would cause an automatic internal disabling of the servo amplifier. If function OxMODE = is selected, the enable signal is high, if the line voltage is applied and the charging of the link capacitors is finished. The drive is disabled, if the DC-link voltage wents under the threshold VBUSMIN. |
O1MODE=22 | Zero_pulse | The zero mark/pulse (HIGH-signal) is indicated by the encoder-emulation. This function is only use-ful at very low velocities. Vmax = 15000 / ENCOUT e.g. ENCOUT=256 Pulses/Rev Vmax = 58 rpm |
O1MODE=23 | Slot-DPR | This configuration enables the possibility to output a state from the Slot board (mem DPR Slot Board Offset 0x3E4). If no Slot board is available, this configuration is equal to OxMODE=0. If a Device-Net option board is plugged in the drive, this setting enables access of Device-Net to digital output 1 |
O1MODE=24 | Ref_OK | The output signals High, if a reference point is available. Reference traverse (homing) has been carried out, or a reference point has been set. (see NREF) |
O1MODE=25 | Reserved | |
O1MODE=26 | Reserved | |
O1MODE=27 | Reserved | |
O1MODE=28 | Posreg.0 | The preset function of the corresponding position register 0 is indicated by a HIGH-signal. Valid only with expansion card -I/0-14/08- . |
O1MODE=29 | Posreg.5 | The preset function of the corresponding position register 5 is indicated by a HIGH-signal. Valid only with expansion card -I/0-14/08- . |
O1MODE=30 | OR-Operation of all Posreg. | The digital output is set if a cam is active. A cam is defined by the position register P1..P16. This registers should be used two by two example: cam 1: P1 and P2 cam 2: P5 and P6 cam 3: P11 and P12 The OxTRIG-variable is used to activate the cam monitoring. The corresponding mask for this example is: OxTRIG = 3123 (Hex-description 0x0C33) The output is set to high level, if any of this cams is active. example 2: O1MODE=30 O1TRIG=3 (Hex 0x0003) O2MODE=30 O2TRIG=3120 (Hex 0x0C30) Output 1 is active if cam 1 is set (P1 und P2). Output 2 is active if cam 2 (P5,P6) or cam 3 (P11,P12) is set. |
O1MODE=31 | Analog SW1< O1TRIG | The output is high, if the analog input voltage at analog input 1 is lower than the threshold O1TRIG. The auxiliary variable O1TRIG is given in mV (with sign). |
O1MODE=32 | Analog SW1> O1TRIG | The output is high, if the analog input voltage at analog input 1 is higher than the threshold O1TRIG. The auxiliary variable O1TRIG is given in mV (with sign). |
O1MODE=33 | Analog SW2 < O1TRIG | The output is high, if the analog input voltage at SW2 is lower than the threshold O1TRIG. The auxiliary variable O1TRIG is given in mV (with sign). |
O1MODE=34 | Analog SW2 > O1TRIG | The output is high, if the analog input voltage at SW2 is higher than the threshold O1TRIG. The auxiliary variable O1TRIG is given in mV (with sign). |
O1MODE=35 | Internal Enable | The state of the internal ENABLE signal is mirrored on the digital output. If the setiings are: MBRAKE=0, STOPMODE=0 and ACTFAULT=0, the function is similar to O1MODE=21. If one of the three variables is "1", the output changes to low, when the drives starts to dec to "0". If O1MODE=21, the output is low, if the drive has stopped and has disabled the output stage. |
O1MODE=36 | Logical OR: DRVSTAT - O1TRIG | This function makes a OR operation between the Bit-variable DRVSTAT and a Bit mask given by O1TRIG. The result is present at output 1. |
O1MODE=37 | Logical AND: DRVSTAT -O1TRIG | This function makes a AND operation between the Bit-variable DRVSTAT and a Bit mask given by O1TRIG. The result is present at output 1. |
O1MODE=38 | Logical OR: TRJSTAT - O1TRIG | This function makes a OR operation between the Bit-variable TRJSTAT and a Bit mask given by O1TRIG. The result is present at output 1. |
O1MODE=39 | Logical AND: TRJSTAT - O1TRIG | This function makes a AND operation between the Bit-variable TRJSTAT and a Bit mask given by O1TRIG. The result is present at output 1. |
O1MODE=40 | Logical OR: POSRSTAT - O1TRIG | This function makes a OR operation between the Bit-variable POSRSTAT and a Bit mask given by O1TRIG. The result is present at output 1. |
O1MODE=41 | Logical AND: POSRSTAT - O1TRIG | This function makes a AND operation between the Bit-variable POSRSTAT and a Bit mask given by O1TRIG. The result is present at output 1. |
O1MODE=42 | This function enables a temperature warning. If one of the three internal measured temperatures reaches the trip level, the digital output ist set to high. After the selected delay time given in O1TRIG the drive generates a error message and disables the output stage. The delay time has the range 0...30000 msec and effects following temperatures: Motor temperature TEMPM, threshold MAXTEMPM Heatsink temperature TEMPH, Threshold MAXTEMPH Ambient temperature TEMPE, threshold MAXTEMPE Start Firmware 3.41 |
|
O1MODE=43 | The sign of the actual velocity | OUTPUT1 = 0 V > VEL0 This function is available starting firmware version 4.01. |
O1MODE=44 | Velocity In-Position (active high) | The output 1 is set, if the absolute of the difference between the internal velocity command and the actual velocity is smaller than O1TRIG. The size of the window (O1TRIG) is given in valid velocity units (VUNIT). (4.30) |
O1MODE=45 | Velocity In-Position (aktive low) | The output 1 is set, if the absolute of the difference between the internal velocity command and the actual velocity is bigger than O1TRIG. The size of the window (O1TRIG) is given in valid velocity units (VUNIT). (4.30) |
O1MODE=46 | Current in Window (high active) | The digital output 1 is set, if the absolute of the difference between current command and actual value is smaller than the window, defined by O1TRIG. The window is given in mA. |
O1MODE=47 | Current not in Window (low active) | The digital output 1 is set, if the absolute of the difference between current command and actual value is greater than the window, defined by O1TRIG. The window is given in mA. |
O1MODE=48 | Logical NOR: DRVSTAT - O1TRIG | This function makes a inverted OR operation between the Bit-variable DRVSTAT and a Bit mask given by O1TRIG. The result is present at output 1. (starting with 4.92) |
O1MODE=49 | Logical NAND: DRVSTAT -O1TRIG | This function makes a inverted AND operation between the Bit-variable DRVSTAT and a Bit mask given by O1TRIG. The result is present at output 1. (starting with 4.92) |
O1MODE=50 | Logical NOR: TRJSTAT - O1TRIG | This function makes a inverted OR operation between the Bit-variable TRJSTAT and a Bit mask given by O1TRIG. The result is present at output 1. (starting with FW 4.92) |
O1MODE=51 | Logical NAND: TRJSTAT - O1TRIG | This function makes a AND operation between the Bit-variable TRJSTAT and a Bit mask given by O1TRIG. The result is present at output 1. (starting with 4.92) |
O1MODE=52 | Logical AND: POSRSTAT - O1TRIG | same as O1MODE = 41 but the output is for PTBASE * 250 us on high level |
O1MODE=53 | Master slave synchron | output is se, if master and slave are synchronized (see also IN1MODE = 51 |